VT7600 series Protocol Implementation Conformance Statement (PICS)
Vendor Name: Vykon
Vendor ID: 140
Product Name: VT7600 Thermostat Series
Product Model Number:
VT7600A5X28B, VT7600B5X28B, VT7605B5X28B, VT7607B5X28B,
VT7600H5X28B, VT7652A5X28B, VT7652B5X28B, VT7656B5X28B, VT7657B5X28B and
VT7652H5X28B.
Product Description:
The VT76xx series BACnet communicating thermostat have been specifically designed for RTU and heatpump
applications to be monitored on a BACnet MS-TP® network.
Supported BACnet Services
The BACnet
communicating thermostat meets all requirements for designation as an Application Specific Controller
(B-ASC). The BACnet thermostat series supports the following BACnet Interoperability Building Blocks (BIBBs).
Application Service Designation
Data Sharing – Read Property - B DS-RP-B
Data Sharing – Read Property Multiple - B DS-RPM-B
Data Sharing – Write Property - B DS-WP-B
Device Management - Device Communication Control - B DM-DCC-B
Device Management – Dynamic Device Binding - B DM-DDB-B
Device Management – Dynamic Object Binding - B DM-DOB-B
Note 1: The thermostat does not support segmented requests or responses.
Note 2: Time synchronization can be made through a network even if the thermostat does not support the full date.
Therefore, the device cannot claim conformance to the DeviceManagement – TimeSynchronization - B