Installer configuration parameter menu
- Configuration can be done through the network or locally at the thermostat.
- To enter configuration, press and hold the middle button “Menu for 8 seconds
- If a password lockout is active, “Password” is prompted. Enter password value using the “up” and “down
arrows and press “Yes” to gain access to all configuration properties of the thermostat. A wrong password
entered will prevent local access to the configuration menu.
- Once in the configuration menu, press the “No” button repetitively to scroll between all the available
parameters.
- When the desired parameter is displayed, press “Yes” to adjust it to the desired value using “up” and “down
arrows. Once set, press “Yes” to scroll to the next parameter.
Configuration
parameters
Significance
Default value
Adjustments
Pswrd
Configuration parameters menu access
password
Default value = 0 ( no password
prompted )
This parameter sets a protective access password to
prevent unauthorized access to the configuration menu
parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu.
Range is: 0 to 1000
Com addr
Thermostat networking address
Default value = 254
Range is: 0 to 254
Conditional parameter to BACnet MS-TP models
(VT76xxX5x28B)
Conditional parameter to Wireless models
(VT76xxX5x28W)
This parameter will only appear when a BACnet or
wireless network adapter is present. If the thermostat is
installed as a stand-alone unit or with an Echelon
adapter, this parameter will not be used or displayed
- For BACnet MS-TP models valid range to use is
from 1 to 127. Default value of 254 disables BACnet
communication for the thermostat.
- For wireless models valid range is 0 to 254 with a
maximum of 30 thermostat per VWG
PAN ID
Personal Area Network Identification
Default value = 0
Range is: 0 to 500
Conditional parameter to Wireless models
(VT76xxX5x28W)
This parameter will only appear when a wireless network
adapter is present. If the thermostat is installed as a stand-
alone unit or with a BACnet or Echelon adapter, this parameter
will not be used or displayed
This parameter (Personal Area Netw
ork Identification) is used
to link specific thermostats to a single specific Vykon JACE
with wireless network adapter. For every thermostat reporting
to a JACE (maximum of 30 wireless thermostats), be sure you
set the SAME PAN ID value both at the JACE and the
thermostat(s).
The default value of 0 is NOT a valid PAN ID. The valid range
of available PAN ID is from 1 to 500