11
List of Property Enumeration Sets for MV Objects
Object Name Object ID BACnet Index Text Default value
1 Cooling Only
2 Heating Only
3 Cooling & Reheat
4 Heating & Reheat
5 Cool/Heat4P
Sequence of
Operation
MV 15
6 Cool/Heat4P&Reht
Heating Only
1 Off
2 Auto
3 Cool
System Mode
Note 1
MV 16
4 Heat
Note 2
Fan Mode
Note 3
MV 17 1, 2, 3 or 4
Note 4 Note 5
1 Local Occupancy
2 Occupied
Occupancy
Command
MV 18
3 Unoccupied
Depends on network
command
1 Level 0
2 Level 1
3 Level 2
4 Level 3
5 Level 4
Keypad Lockout MV 19
6 Level 5
Level 0
Note 1 Enumeration sets for MV16 depends on Sequence of Operation (MV15) value upon device
discovery. If required enumeration is not present, set MV15 to desired value and rediscover MV16 object.
Available enumeration will now reflect required configuration.
Note 2 Default value of MV16 depends on MV15 value upon device discovery
MV15 Index Function
Default Value is
BV50 Enabled
Default Value is
BV50 Disabled
1 Cooling Only Cool Cool
2 Cooling with Reheat Auto Heat
3 Heating Only Heat Heat
4 Heating with Reheat Heat Heat
5 Cooling/Heating 4 Pipes Auto Heat
6 Cooling/Heating 4 Pipes with Reheat Auto Heat
Note 3 Enumeration sets for MV17 depends on Fan Mode Sequence (MV58) value upon device discovery.
If required enumeration is not present, set MV58 to desired value and rediscover MV17 object. Available
enumeration will now reflect required configuration.
Note 4 & 5 Available state text and default value depends on Fan Mode Sequence (MV58) value upon
device discovery.
MV17 Index Function MV58 State Text Index Default Value
1 1 Low - 2 Med - 3 High High
2 1 Low - 2 High High
3 1 Low - 2 Med - 3 High - 4 Auto High
4 1 Low - 2 High - 3 Auto High
5 1 Auto -2 On Auto
Comentários a estes Manuais