Configuration Objects
The following objects and group objects should be typically used for configuration purposes:
¾ General Options 1 Group GRP 45 and its complete list of objects;
¾ General Options 2 Group GRP 55 and its complete list of objects;
¾ Humidity Models Configuration Options Group GRP 69 and its complete list of objects;
¾ Output Configuration Options Group GRP 74 and its complete list of objects.
If your BAS allows you to remove objects, Vykon recommends removing all configuration objects once your
setup is complete. This will prevent unnecessary network polling and traffic.
Wiring guide
Overview
Vykon uses EIA-485 as the physical layer between their devices and supervisory controllers
For clarity we will use the term “Device” to represent any product with an active EIA-485 network
connection, including Vykon and non-Vykon controllers.
Summary Specifications:
Parameter Details
Media
Twisted pair 22AWG-24 AWG, shielded recommended
Characteristic Impedance
100-130 ohms
Distributed capacitance
Less than 100 pF per meter (30 pF per foot)
Maximum length per segment
1200 meters (4000 feet) Note: AWG 18 cable
Polarity
Polarity sensitive
Multi-drop
Daisy-chain (no T connections)
Terminations
1. Vykon’ devices are installed at both ends of the MSTP
network:
120 Ohms resistor should be installed at each end.
2. A Vykon device is installed at one end of the MSTP
network and a 3
rd
party device is installed at the other
end:
Install an End-Of-Line resistor value that matches the 3 rd
party device instruction regarding the End-Of-Line resistors
3. 3
rd
party devices are installed at both ends of the MSTP
network:
Follow the 3
rd
party device instructions regarding the End-
Of-Line resistors.
Network Bias Resistors
510 ohms per wire (max. of two sets per segment)
Maximum number of nodes per
segment
64 (Vykon devices only)
Maximum number of nodes per
network
128
Baud rate
9600, 19200, 38400, 76800 (Auto detect)
Table 1: Summary of Specifications for a Vykon’ EIA-485 Network