12
Object Name Object ID BACnet Index Text Default value
Heating Valve
Status
Note 6
MV 26
Note 7 Note 7 Note 7
Cooling Valve
Status
Note 8
MV 27
Note 9 Note 9 Note 9
1 Off
2 Low
3 Med
Fan Status MV 28
4 High
Off
1 Occupied
2 Unoccupied
3 Temporary Occupied
Effective
Occupancy
MV 33
4 Stand-by
Depends on local
occupancy
Note 6 Enumeration sets for MV26 depends on Control Type (BV75) value and Pipe Number (MV52) value
upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and
rediscover MV26 object. Available enumeration will now reflect required configuration.
Note 7 Available object name, state text and default value depends on Control Type (BV75) value and Pipe
Number (MV52) upon device discovery.
BV75 Value MV52 Index
MV26 Object
Name
Function MV26 State Text Index Default Value
1 (2 pipe) Unused Output N/A N/A On/Off
2 (4 pipe)
Heating Valve
Status
1 Closed – 2 Open Closed
1 (2 pipe) Unused Output N/A N/A Floating
2 (4 pipe)
Heating Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped
Note 8 Enumeration sets for MV27 depends on Control Type (BV75) value and Pipe Number (MV52) value
upon device discovery. If required enumeration is not present, set BV75 and MV52 to desired value and
rediscover MV27 object. Available enumeration will now reflect required configuration.
Note 9 Available object name, state text and default value depends on Control Type (BV75) value and Pipe
Number (MV52) upon device discovery.
BV75 Value MV52 Index
MV27 Object
Name
Function MV26 State Text Index Default Value
1 (2 pipe)
Heat/Cool Valve
Status
1 Closed – 2 Open Closed On/Off
2 (4 pipe)
Cooling Valve
Status
1 Closed – 2 Open Closed
1 (2 pipe)
Heat/Cool Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped Floating
2 (4 pipe)
Cooling Valve
Status
1 Stopped - 2 Opening - 3 Closing Stopped